+86 18138349857

staceychow@smartlaffey.com

prev
next

KNX 10A Switch Actuator

Model: MR0410; MR0610; MR0810; MR1210; MR1610; MR2010; MR2410
Main Input: 4/6/8/12/20/24 circuits, each circuit 250V AC(50/60Hz)
KNX Bus Voltage: 21-30VDC ; KNX Bus Current: ≤20mA
Bus Power: ≤ 360mW ; Shell Material: PA66
Size (mm): 72mm x 90mm x 64mm 4 Circuits (MR0410)
145mm x 90mm x 64mm 6/8/12 Circuits (MR0610/MR0810/MR1210)
218mm x 90mm x 64mm 16/20/24 Circuits (MR1610/MR2010;MR2410)
Contact us + Leave a message +


The 10A series switching actuator modules are modular installation devices with 4-circuits, 6-circuits, 8-circuits, 12-circuits, 16-circuits and 20-circuits outputs. EIB bus terminals are connected to EIB/KNX system, and ETS software (version ETS4.0 or above) is used for physical address allocation and parameter setting.

The maximum load current for output of each 10A series switching actuator module is 10A, including 4, 6, 8, 12, 16 and 20 intelligent relays. Each circuit can independently control the switch of 2000W lamps. The above is only for resistive load lamps, the actual use of 80% of the power to drive the resistive load will be more appropriate. To the inductive load and capacitive load, especially in the case of multiple lamps in parallel, the loads that can be carried will be reduced. Although the power is unchanged, the inrush transient current will increase, easy to melt relay contact, so for the inductive load and capacitive load, it is advisable to use 1/5 or 1/6 of the maximum current commonly, even some inferior LED lamp loads require 1/8 of the maximum current.

10A series switching actuator module with manual control buttons, LED indicates the status of each circuit switch. The 10A series switching actuator module has 4 dry contact input interfaces, which can input control instructions such as switches, curtains, dimming, and scenes.

Function description:

(1)Independent control of 4/6/8/12/16/20/24 circuits lights / loads;

(2)With manual key switch; relay has magnetic holding function

(3)Delay on / off function;

(4)Timer off and cycle switch function;

(5)With field save and restore functions;

(6)Status value query reply function;

(7)Selection function of relay switch state after bus power failure and voltage recovery;

(8)With scene combination control function;

(9)The 4/6/8/12/16/20/24 circuits switching actuator module has an I / O dry contact input interface, which can input control instructions such as switches, curtains, dimming, and scenes; it can directly link fire emergency lighting;

(10)I / O wiring communication distance: less than 10m.


How to order

You can get your KNX 10A Switch Actuator solution by filling out the form below and we will contact you immediately

  • *
  • *
  • *
Copyright © Guangdong Daming Laffey Electric Co., Ltd. Privacy statement Terms & conditions Sitemap